1 ###############
2 Ebyte M31 I/O
3 ###############
4
5 The ``driver/m31`` package defines one host and up to fifteen expansion
6 modules. A module's slice index is its slot. The host has eight digital
7 inputs and eight digital outputs. Mixed expansions add eight of each,
8 input expansions add sixteen inputs, output expansions add sixteen
9 outputs, and analog expansions add eight voltage outputs.
10
11 Each point uses ``m{slot}.di{channel}``, ``m{slot}.do{channel}``, or
12 ``m{slot}.ao{channel}``. Inputs, coils, and analog registers have
13 independent zero-based address ranges that continue across modules.
14 Configure every physical analog output channel for zero through ten
15 volts before operation. The driver does not configure the module's
16 output range. Analog registers represent zero through ten volts as zero
17 through 10000. Hardware pulse widths are whole milliseconds from 50
18 through 65535. Their width registers start at ``0x30d4`` and their
19 output-mode registers start at ``0x32c8``, both indexed by coil address.
20 Mode zero is level control and mode one is pulse control.
21
22 Descriptors use manufacturer ``ebyte`` and firmware ``unknown``. The
23 package does not read the host identity registers. Pulse capabilities
24 accept commands but do not report transient coil state. Input
25 capabilities are read-only.
26
27 Tests verify topology and descriptor values without a physical module.
28 They do not confirm physical expansion limits or relay timing under
29 load. The conservative sixteen-module limit includes the host.
30
31 ***************
32 Modbus client
33 ***************
34
35 ``NewTCPClient`` supplies a caller-owned, serialized connection through
36 ``Client``. Connect selects the configured unit and has a two-second
37 timeout. A request has a one-second write deadline and a two-second
38 response deadline, both measured from its start. Caller deadlines and
39 cancellation can stop it earlier. Each response must match the
40 transaction, unit, function, length, and write acknowledgement.
41 Supported functions are 01, 02, 03, 05, 15, and 16. No external Modbus
42 package is required.
43